WR 50E47 - 50F47 TROUBLESHOOTING

VISUAL CHECK CHART 1

Call for Heat. Thermostat Contacts Closed.
       

Does the Silicone Ignitor Warm Up and Glow Bright Red after Prepurge Cycle Is Complete?

No - Go Right

Yes - Go Down

Is 25 Volts Present Across Module Termals TH & TR?

No - Go Right

Yes - Go Down

Is 25 Volts Present Across the Secondary of the Transformer?

No - Go Right

Yes - Go Down

Is 120 Volts Present Across the Primaryh of the Transformer?

No - Go Right

Yes - Go Down

Replace Open Limits or Fuses in the 120 Volt Supply. Energize the System and Check for Proper Operation.

Go to Chart 2

DISCONNECT ELECTRIC POWER TO THE SYSTEM AT THE MAIN FUSE OR CIRCUIT BREAKER PANEL

Continue Down

Replace Open 25 Volt Limits or Thermostat. Energize the System and Check for Proper Operation.

Replace 24 Volt Control Transformer. Energize the System and Check for Proper Operation.
 
 

Unplug ignitor from wire harness and connect ohmmeter across ignitor leads. Is resistance within the equipment manufacturers specifications?

No - Go Right

Yes - Go Down

Replace Ignitor. Connect Electric Power to System at Main Fuse or Circuit Breaker Panel.

Go Right

Energize System. Ignitor should Glow Red and Deenergize after Trial for Ignition Period.

Yes - Go Right

No - Go Down

System is functioning properly.
 

Connect Ohmmeter across IGN & L terminals of module.

Continue Down
 

Replace Ignition Module. Energize System and Check for Proper Operation.
 
 

Connect Electric Power to System at Main Fues or Circuit Breaker Panel. Energize System.

Go Right

Does Continuity Exist between IGN & L after Prepurge Cycle?

No - Go Right

Yes - Go Down

Replace Module. Energize System and Check for Proper Operation.
 
   

Correct discontinuities in ignitor harness or connections. Energize System and Check for Proper Operation.
   

Back to 50E47 Troubleshooting Guide